What precautions should be taken when applying fireproof coating to steel structures by brushing?


Release date:

2022-02-21

Author:

Zhengxiang Fireproof Materials

When introducing the application of ultra-thin steel structure fireproof coatings, we briefly reviewed the brush‑coating process. However, in actual construction, brush coating is far more than just theoretical knowledge. Below, we will examine the specific steps and related considerations for applying steel structure fireproof coatings by brushing.

  When introducing the application of ultra-thin steel structure fireproof coatings, we briefly reviewed the brush‑coating process. However, in actual construction, brush coating is far more than just theoretical knowledge. Below, we will examine the specific steps and related considerations for applying steel structure fireproof coatings by brushing.
  1. Selection of equipment and operational considerations for brush application of fire-resistant coatings on steel structures:
  For brush application, a brush width of 3 or 4 mm is recommended. Apply the coating with moderate material pickup and even pressure to ensure a smooth finish. Allow each coat to dry completely before applying the next. When applying the second coat, use a putty knife to level any raised areas locally, ensuring overall surface smoothness.
  2. Control of brushing intervals and coating thickness for fireproof coatings on steel structures:
  Brush application must also be carried out in multiple coats, with each coat applied only after the previous one has completely dried and cured. Under conditions of good ventilation, low relative humidity, and clear weather, the interval between recoats is approximately 24–48 hours (the interval for the first coat may be shortened accordingly). When relative humidity exceeds 90%, during rainy weather, or when condensation forms on the surface of steel components, brush application should not be performed unless additional measures are taken. The thickness of each coat should not exceed 1.5 mm (with the first coat limited to no more than 0.5 mm) to prevent sagging due to excessive coating thickness. During brush application, the applicator must carry a wet‑film thickness gauge to verify that each coat does not exceed the specified limits (1.5 mm for subsequent coats; 0.5 mm for the first), and repeat the process as described until the design‑specified total thickness is achieved.
  When applying fireproof coatings to steel structures by brushing, the work often proceeds at a fast pace and demands a high level of skill from the applicators. Therefore, construction teams must carefully observe the aforementioned precautions when selecting this application method.