Understanding the Properties of Thin-Film Fire-Retardant Coatings in One Minute
Release date:
2022-06-22
Author:
Zhengxiang Fireproof Materials
Thin‑type fire‑retardant coating is a type of fire‑protective coating applied to the surface of steel structures. When exposed to fire, the coating expands and foams to form a charred, insulating protective layer that blocks oxygen, thereby slowing the rate at which the steel structure heats up, preventing rapid temperature rise in the steel members, and increasing the fire‑resistance duration of the steel structure.
Thin-type fireproof coating A fire-retardant coating applied to the surface of steel structures. When exposed to fire, the coating expands and foams to form a charred, insulating protective layer that blocks oxygen, thereby slowing the rate of temperature rise in the steel structure, preventing rapid heating of steel components, and increasing the fire-resistance duration of the steel structure.
I. Characteristics of Thin-Film Fire-Retardant Coatings
Thin-type fireproof coating It meets fire protection requirements, with a fire-resistance rating of 0.5 to 2.5 hours, and is suitable for columns, beams, roof load-bearing members, and evacuation staircases in single-story supports within buildings of Class I fire resistance. It is also used for steel structural components supporting single- and multi-story columns, beams, roof load-bearing members, and evacuation staircases. The fire-resistance rating ranges from Class II to Class IV. Its technical specifications comply with the national standard GB 14907—2002. The coating is easy to apply, non-toxic, thin, and provides effective fire protection; it has a smooth surface and excellent decorative appeal. Additionally, it exhibits superior aging resistance, adhesion, and durability, remaining free from chalking for many years. Thin-type intumescent fireproof coatings have been widely adopted in construction, and recent advances in technology further address public needs. However, it is essential first to understand the product’s performance characteristics to ensure its more rational application.
II. Methods for Ensuring the Fire-Resistant Performance of Thin-Film Fire-Retardant Coatings
(1) Bond strength shall comply with the relevant standards. Incoming material quality must be strictly controlled. Foreign objects are strictly prohibited during construction, and operations by other trades on the same work surface should be avoided whenever possible. Prior to construction, mix proportion tests shall be conducted under identical conditions (same humidity, same temperature, same working environment), and the determined proportions must be strictly followed during application. The base putty shall also be inspected before use.
(2) Prior to coating, remove oil, dust, dirt, release agents, and other contaminants from the steel surface or the substrate of the existing coating. (If a rust-preventive treatment has been applied, it shall be properly removed, and the thickness of the rust-preventive coating shall comply with design requirements.) During coating, avoid contamination caused by other surrounding factors.
(3) Coating tools, such as roller brushes, brushes, and spray guns, should be standardized and tested in advance. The working environment should be maintained between 5°C and 38°C, with relative humidity not exceeding 85%. Operations should not be conducted in rainy weather, when wind speeds exceed 5 m/s (level 4), or when condensation is present on the component surfaces. Protect the coating from rain for 4 hours after application. In case of light rain, stop work and properly protect the painted surface.
(4) Construction personnel must undergo specialized training and assessment, and process monitoring must be strictly enforced to prevent missed or excessive coating applications. The work is currently under construction. Gently tap the dry film coating with a 0.75–1 kg hammer to verify firm adhesion. Before applying the next coat, use a scraper to smooth out any uneven areas. If cracks in the thin coating exceed 0.5 mm (or in the thick coating exceed 1.0 mm), localized repairs are required before proceeding. When fiberglass cloth reinforcement is specified, it must be applied by qualified personnel to avoid applying too many or too few layers of pressure.
Thin-type fireproof coating When exposed to fire, it rapidly expands to form an intumescent protective layer, slowing the transfer of heat to the substrate surface, and is widely used in the national economy.