Thin‑type fire‑proof coatings, also known as thin‑film fire‑proof coatings for steel structures, are primarily used on steel frameworks. They not only provide excellent fire protection but also offer a decorative finish. These coatings effectively extend the fire resistance of structural elements, enhance the safety performance of buildings, and buy valuable time for rescue operations.
Thin-type fireproof coating It is what we call thin‑film intumescent fire‑protective coating for steel structures, primarily used on steel frameworks. Not only does it provide excellent fire protection, but it also offers a decorative finish. It can effectively extend the fire resistance of equipment, enhance the safety of buildings, and buy valuable time for rescue operations.
Thin-film fireproof coatings are water-based fireproof coatings for steel structures, applied to the surface of steel components. When exposed to fire, the coating expands and foams to form a charred, insulating protective layer that cuts off oxygen, slows the rate of temperature rise in the steel structure, and prevents rapid heating of the steel members, thereby increasing the fire resistance duration of the steel structure.
Thin‑type fire‑protective coatings can meet fire‑protection requirements, with fire resistance limits ranging from 0.5 h to 2.5 h, and are suitable for columns, beams, roof load‑bearing members, evacuation stairways, and similar elements. In building design, they are used for single‑story braced frames of Class I fire resistance. They are also applied to steel structural members such as single‑ and multi‑story columns, beams, roof load‑bearing components, and evacuation stairways, where the fire resistance rating is between Grade II and Grade IV.
I. Characteristics of Thin-Film Fire-Retardant Coatings
1. Easy to apply and non-toxic.
2. The coating is thin and offers excellent fire resistance.
3. Smooth surface with excellent decorative effect.
4. The coating film exhibits excellent aging resistance, is robust and durable, and remains free from chalking for many years.
5. It has a certain degree of resistance to moisture and to acids and alkalis; it contains no asbestos or formaldehyde, is non-toxic and harmless, and does not harm the environment.
II. Thin-type fireproof coating Construction process
Before applying fireproof coating, the anti-rust primer on the steel member surfaces shall comply with design requirements and current national regulations, and any dust, oil, or other debris on the steel surfaces must be removed. Thin fireproof coatings should be applied before interior finishing to prevent damage from subsequent work. During application, conceal wall, door, window, and mechanical equipment components that do not require fire protection. Prior to painting, thoroughly mix the coating; if it is too thick, add an appropriate amount of water to achieve a spreadable consistency, diluting it until it no longer flows. Use a spray method: at an air pressure of 0.4–0.6 MPa, apply evenly using a gun-type sprayer with a nozzle diameter of 6–8 mm. All coating thicknesses must fully cover the substrate; typically, each layer should not exceed 1 mm, and subsequent layers may only be applied after the previous one has cured. Starting with the second coat, the thickness per application may be increased appropriately, but care should be taken to avoid sagging.
III. Thin-type fireproof coating Things to note
During construction and before the paint has dried and cured, the ambient temperature should be maintained between 5 and 45°C, with relative humidity not exceeding 90%, and adequate ventilation must be ensured. Work should not proceed if condensation is present on component surfaces. Throughout this process, coating thickness should be measured as needed to meet the required fire-resistance rating. When applying by spraying, ensure consistent spray direction to prevent uneven texture and light‑color variations caused by inconsistent grain. For waterborne fire‑retardant coatings, the finished work should be stored indoors or in a shelter to protect it from rain.