What are the advantages of thin-film fireproof coatings?
Release date:
2022-11-28
Author:
Zhengxiang Fireproof Materials
Thin-type fireproof coatings are water-based fireproof coatings for steel structures. Specifically, they are coatings with a thickness greater than 3 mm and less than or equal to 7 mm, which provide decorative effects. When exposed to high temperatures, they expand and thicken, offering a fire resistance duration of up to 2 hours.
Thin-type fireproof coating is a water-based fireproof coating for steel structures. Thin-type fireproof coating It refers to a thin-type fireproof coating for steel structures with a coating thickness greater than 3 mm and not exceeding 7 mm, providing decorative effects, expanding and thickening upon exposure to high temperatures, and offering a fire resistance duration of up to 2 hours.
Intumescent fire‑protective coatings are typically formulated with suitable waterborne polymers as the base, combined with flame‑retardant composite systems, flame retardants, and refractory fibers. For intumescent fire‑protective coatings applied to steel structures, the selected waterborne polymer must exhibit excellent adhesion to the steel substrate, along with good durability and water resistance.

Thin‑coat fire‑protective coatings are more aesthetically pleasing than thick‑coat systems, but less so than ultra‑thin intumescent coatings for steel structures. Their typical fire resistance is less than 2 hours. Consequently, they are frequently used in steel‑structure fire‑protection projects where a fire resistance of under 2 hours is required, and they are usually applied by spray coating.
Paint is applied to the surface of steel members; upon exposure to fire, the coating expands to form a charred, fire-resistant insulating layer that cuts off oxygen, slows the temperature rise of the steel structure, and prevents rapid heating, thereby increasing the fire-resistance duration of the steel structure. This product meets fire protection requirements, with fire-resistance ratings ranging from 0.5 h to 2.5 h, and is suitable for columns, beams, roof load-bearing members, evacuation stairways, and similar applications. It is used in building designs requiring a Class I fire rating for single-story bracing, as well as for bracing steel members in single- and multi-story structures, including columns, beams, roof load-bearing components, and evacuation staircases. The fire-resistance rating ranges from Class II to Class IV. Its technical specifications comply with the national standard GB 14907—2002. Thin-type fireproof coating What are its advantages? Let’s analyze them below.
1. Easy to apply and non-toxic.
2. The coating is thin and offers excellent fire resistance.
3. Smooth surface with excellent decorative effect.
4. The coating film exhibits excellent aging resistance, is robust and durable, and remains free from chalking for many years.
Thin-type fireproof coating What is the construction process? Let’s analyze it below.
Before applying fire‑retardant coating, the rust removal and anti‑corrosion primer on steel members shall comply with design requirements and current national regulations, and all dust, oil, and other contaminants must be thoroughly removed. Fire‑retardant coating should be applied prior to interior finishing and protected from damage during subsequent work. During application, cover walls, doors, windows, machinery, and other components that do not require fire protection. Before painting, stir the coating thoroughly until uniform. If the coating is too thick, dilute it with an appropriate amount of water to achieve a suitable consistency for brushing; it should not run. This product is intended for spray application; apply evenly using a hopper gun with a nozzle diameter of 6–8 mm at an air pressure of 0.4–0.6 MPa. The coating thickness should fully cover the substrate surface, generally not exceeding 1 mm. Proceed to the next coat only after the preceding coat has fully dried. Starting with the second coat, the thickness per pass may be increased slightly, provided it remains free of runs.
What are the precautions for thin-type fireproof coatings? Let’s analyze them below.
During construction and before the coating has dried and cured, the ambient temperature should be maintained between 5°C and 45°C, with relative humidity not exceeding 90%, and adequate ventilation must be ensured. Construction should not proceed if condensation is present on the component surface. Throughout the application process, the coating thickness should be measured as needed to meet the required fire-resistance rating. When spray-applied, ensure a consistent spraying direction to prevent uneven texture and color variations. This product is a water-based fire-retardant coating; therefore, it should be stored indoors or under shelter to avoid exposure to rain during and after application.