What are the common issues and precautions in the application of fire-resistant coatings for steel structures?
Release date:
2023-01-16
Author:
Zhengxiang Fireproof Materials
What are the common problems and precautions during the application of fireproof coatings for steel structures? I. Main Quality Issues in Steel Structure Fireproof Coating Application Through the coating process performed by qualified engineers, a fire-resistant layer is formed on the surface of steel components, completing the entire steel structure fireproofing procedure. The application of fireproof coatings is also part of their secondary manufacturing process. Improper application can adversely affect the overall quality of the steel structure fireproofing project.
Fireproof coating for steel structures What are the issues and precautions during construction?
I. Main Problems in the Construction Quality of Fire-Retardant Coatings for Steel Structures
Through the application of paint by qualified engineers, a fire-resistant coating is formed on the surface of steel members, completing the entire process of fireproofing steel structures. The application of fire-retardant coatings also constitutes a secondary production stage for these materials. Improper application can compromise the quality of the fireproofing work. The main issues during application are:
1. Neglecting to clean the substrate surface can compromise the performance of fire-retardant coatings.
2. The construction team lacks the requisite qualifications and has limited technical expertise.
3. There was no scientifically sound construction plan prior to work, and during construction, quality could not be rigorously inspected in accordance with technical standards.
4. The final acceptance of fireproof coatings relies solely on visual inspection and coating thickness measurement, lacking rigorous acceptance criteria and testing methods.
5. Pursuing aesthetic appearance and smoothness by sanding the fireproof coating or applying ordinary decorative paint on its surface, among other practices. This makes it difficult to ensure the coating’s technical performance.
II. Fireproof coating for steel structures Construction Precautions
1. Surface preparation of the substrate for fireproof coatings shall be rigorously inspected as a separate procedure. Remove dust, metal filings, rust, grease, and other substances that may impair adhesion, and apply appropriate anti-corrosion treatment to the substrate. The primer and topcoat of the fireproof coating system must be properly matched, and the primer must not corrode the steel.
2. When applying fireproof coating by spraying, it is essential to control the coating’s consistency, the air compressor pressure during spraying, and the distance between the spray nozzle and the component. During application, excessive overspray or poor coverage indicates that the process parameters are inappropriate and should be adjusted. Do not add excessive thinner to the coating; otherwise, its proper application viscosity will be reduced, and the coating will fail to adhere to the steel structure surface.
3. Fireproofing spray protection for steel structures shall be carried out by a qualified and trained construction team. A rigorous construction plan shall be developed based on the project’s characteristics and product selection. Physical and chemical properties of the coating may be tested by sampling in accordance with specified proportions prior to the project. During application, different areas of intumescent fireproof coating should be selected to evaluate its expansion performance.
4. Upon completion of the work, in addition to measuring coating thickness, visually inspect the coating for color uniformity, leaks, and cracks. Use a 0.75–1 kg hammer to tap the coating and assess its strength. Check the coating’s flatness with a 1-meter straightedge. The coating shall be smooth, free of noticeable depressions, firmly bonded, and exhibit no chalking, looseness, or laitance; raised aggregates must be removed, and there shall be no areas of missed application, powdering, or obvious cracking.
5. During paint application, apply subsequent coats only after the previous coat has substantially dried and cured. The coating protection method, number of coats, and thickness of the protective layer shall be determined according to the construction design requirements. Each coat should be applied at an appropriate thickness; avoid applying it too thickly or rolling it unevenly to prevent compromising coating quality. Follow the painting process strictly to avoid creating safety hazards in the building due to rushing the schedule. Image
6. The coating thickness shall comply with the design value, and thicker coatings shall be applied at joints. Requirements for the spraying area, surface treatment of components, joint filling, paint preparation, number of spray coats, quality control, and acceptance procedures must all conform to the provisions of the current national standard “Technical Code for Application of Fire‑Resistant Coatings for Steel Structures” (CECS24-2020). During construction, the coating thickness shall be inspected using a thickness gauge. If widespread and relatively wide cracks appear in the coating, the process parameters and the coating mix ratio should be reviewed and analyzed to ensure they are correct.